The CA 6117 is presented as the ALL-IN-ONE for the control of electrical installations according to national and international standards (IEC 60364-6, NF C 15-100, VDE 100, FD C 16-600, etc.). It combines design, ergonomics, performance, speed and precision.
Adapted for all types of neutral regimes (TT, TN, IT), it is appropriate for all sectors of use: industry, tertiary, housing.
Ergonomics
Sturdy and compact, the CA 6117 is designed for quick and efficient commissioning. The user sees all essential results at a glance thanks to its large backlit color graphic LCD screen.
A rotary switch, located on the front of the instrument, allows direct access to all functions. Numerous acoustic and visual symbols offer a quick interpretation of the results according to the standards. Contextual help for each function guides the user step by step or only if necessary. Its storage capacity allows you to save up to 1,000 tests. The CA 6117 has a USB output for data recovery.
Measurements...
The CA 6117 offers high performance and excellent measurement stability, even in a disturbed industrial environment. All the necessary measurements for the control of an electrical installation are available: continuity, resistance, insulation, earth and selective earth, loop impedances, type A and AC differentials. The CA 6117 also allows measuring voltage, frequency, current using a clamp, active power, harmonics and phase rotation.
Even better: equipped with a fuse box integrated in the instrument, the CA 6117 allows you to make measurements on type B RCDs. It also measures the voltage drop.
Designed and manufactured in France, the CA 6117 has been developed according to the processes of environmental design.
Analysis of the results
The measurements made with the CA 6117 can be processed with the multi-product expert operating software DataView®. DataView® automatically recognizes the instrument when connected to the PC, and opens the corresponding menu. In the form of a directory tree, it offers the user direct access to the data stored in the instrument, its configuration, etc.
It has different predefined report models, which comply with regulatory requirements.
The user can create your own models, according to your needs.
The ICT software comes as standard and includes, for a simplified and fast analysis of the recorded measurements, the following functions: data recovery, instrument configuration, measurement campaign customization with transfer to the instrument and edition of reports.
Accessories
Supplied in a transport bag with a large number of accessories, it also comes standard with a hand strap and a 4-point strap for “hands-free” use.
Continuity / Resistance:
I > 200 mA / 39.99 Ω / 0.01 Ω / ± (1.5% of the measurement + 2 cts) 12 mA / 39.99 Ω & 399 .9 Ω / 0.01 & 0.1 Ω /± (1.5 % of the measurement + 5 cts) with acoustic signal
Insulation:
Nominal voltage: Utest: 50 / 100 / 250 / 500 / 1000 VDC
Range / Resolution / Accuracy: 0.01 MΩ to 2 GΩ / 10 kΩ to 1 MΩ / ±(5% of measurement + 3 cts)
Short Circuit Current: ≤ 3 mA
Ground:
3P Ground: 0.50 Ω to 40 Ω / 0.01 Ω / ±(2% of measurement + 10 cts) • 40 Ω to 15 kΩ / 0.1 Ω to 1 Ω / ±(2 % of the measurement + 2 cts) 15 kΩ to 40 kΩ / 10 Ω / ±(10 % of the measurement + 2 cts)
Others: Resistance measurement of auxiliary probes RH & RS (up to 40kΩ)
Ufk: Meets SEV 3569
Selective 1P Ground: 0.20 Ω to 39.99 Ω - 40 Ω to 399.9 Ω / 0.01 Ω – 0.1 Ω / ±(10 % of the measurement + 10 cts) (ISel by clamp)
Loop impedance (Zi (L-PE) and Zs (L-N or L-L)) – GROUND WITH VOLTAGE 1P:
Live earth (Installation voltage / Frequency): 90 to 500 V / 15.8 a 17.5 Hz - 45 to 65 Hz
High current mode with trip (TRIP) Zs (L-PE) and Zi (L-N or L-L): Max. test current: 7.5 A (0.050) 0.100 Ω a 0.5 Ω / 0.001 Ω / ± (10% of measurement + 20 cts) • 0.5 Ω to 3.999 Ω / 0.001 Ω / ± (5% of measurement + 20 cts) 3.999 to 39.99 Ω / 0 .01 Ω / ± (5% of measurement + 2 cts) • 39.99 Ω to 399.99 Ω / 0.1 Ω / ± (5% of measurement + 2 cts)
Non-tripping mode (NO TRIP)n(only Zs (L-PE)): Test current: 6 mA – 9 mA – 12 mA (to choose) • 0.20 Ω to 0.99 Ω / 0.01 Ω / ± (15 % of the measure + 10 cts); 1.00 to 1.99 Ω / 0.01 Ω / ± (15% of measurement + 3 cts) • 2.00 to 39.99 Ω / 0.01Ω / ± (10% of measurement + 3 cts) 40.00 Ω to 399.9 Ω / 0.1 Ω / ± (5% of measurement + 2 cts) • 400 to 3999 Ω / 1 Ω / ± (5% of measurement + 2 cts)
Calculation of short circuit current; Ik (PFC (Zs)) , I Sc PSCC (Zi): Fault and short-circuit current: 0.1 A to 20 kA
Integrated fuse table
Voltage drop ΔU% (Zi): -40 % to +40 %
Others: Others Measurement of the resistive and inductive components of the impedances Zs and Zi
Type AC, A and F differences:
Installation voltage / Frequency: 90 V to 500 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz
I∆n: 6*/10/30/100/300/500/650/1000 mA (90 V - 280 V) or 6*/10/30/100/300/500 mA (280 V - 550 V) or variable / Ramp and pulse test
Non-trip test: at ½ I∆n – Duration: 1000 ms or 2000 ms
Ramp mode: 0.2 to 0.5 x I∆n (Uf) / 0.3 x I∆n to 1.06 x I∆n in steps of 3.3% x I∆ n
Trip time measurement: 0.2 to 0.5 x I∆n (Uf) / 0.5 x I∆n / 2 x I∆n (selective) / 5 x I∆n ; Pulse: 0 to 500 ms / 0.1 and 1 ms / 2 ms, Ramp Mode: 0 to 200 ms / 0.1 ms / 2 ms
Differences type B, B+ and EV
Installation voltage / Frequency: 90 V to 280 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz
Test in ramp mode I∆n: 6/10/30/100/300/ 500 mA or variable 6-499 mA
Ramp mode test: From 0.2 x I∆n to 2.2 x I∆n
Pulse mode test at 2 x I∆n: I∆n: 6/10/30/100/ 300 mA or variable ≤ 250 mA ; 2.2 x 2 x I∆N
Test in pulse mode at 4 x I∆n: I∆n: 6/10/30/100 mA or variable ≤ 125 mA; 2.4 x 4 x I∆N
Other measurements:
Current via current clamp: 5.0 mA to 19.9 or 199.9 A (depending on the clamp)
Voltage: 0 to 550 AC/DC /DC and 15.8 to 500 Hz
Frequency: 10 to 500 Hz
Phase rotation: 20 to 500 VAC
Active power: single-phase - from 0 to 330 kW in three-phase (Display of the waveform simultaneously voltage and current.)
Harmonics: Voltage and Current / up to range 50 / THD-F / THD-R
Display: Large LCD screen color graphic 5.7” backlit 320 x 240 points
Memory / communication: via USB for data transfer and report creation
Autonomy: up to 24 hours of operation up to 30 hours
Dimensions / Weight: 280 x 190 x 128 mm / 2.2 kg
Protection index: IP 53 / IK04
EMC : IEC 61326-1
Electrical safety: IEC 61010 -1 – 600 V CAT III – 300 V CAT IV – IEC 61557