NEW MODEL CA6116N: Delivery time: 3 to 5 days
Quantity | ||
---|---|---|
The CA 6116N is presented as the ALL-IN-ONE for the control of electrical installations according to national and international standards (IEC 60364-6, NF C 15-100, VDE 100, FD C 16-600, etc.). It combines design, ergonomics, performance, speed and precision.
Adapted for all types of neutral regimes (TT, TN, IT), it is appropriate for all sectors of use: industry, tertiary, housing.
Ergonomics
Solid and compact, the CA 6116N is designed for quick and efficient commissioning. The user sees all the essential results at a glance thanks to its large backlit color graphic LCD screen.
A rotary switch, located on the front of the instrument, allows direct access to all functions. Numerous acoustic and visual symbols offer a quick interpretation of the results according to the standards. Contextual help for each function guides the user step by step or only if necessary. Its storage capacity allows you to save up to 1,000 tests. The C.A 6116N has a USB output to retrieve data.
Measurements...
The CA 6116N offers high performance and excellent measurement stability, even in a disturbed industrial environment. All the necessary measurements for the control of an electrical installation are available: continuity, resistance, insulation, earth and selective earth, loop impedances, type A and AC differentials. The CA 6116N also allows measuring voltage, frequency, current using a clamp, and phase rotation.
Designed and manufactured in France, the CA 6116N has been developed following environmental design processes.
Analysis of the results
Measurements made with the CA 6116N can also be processed with the multi-product expert operating software DataView®. DataView® automatically recognizes the instrument when connected to the PC, and opens the corresponding menu. In the form of a directory tree, it offers the user direct access to the data stored in the instrument, its configuration, etc.
It has different predefined reporting models, which meet regulatory requirements.
The user can create his own models, according to his needs.
The ICT software comes as standard and includes, for a simplified and fast analysis of the recorded measurements, the following functions: data retrieval, instrument configuration, measurement campaign customization with transfer to the instrument and report editing.
Accessories
Supplied in a transport bag with a large number of accessories, it also comes standard with a hand strap and a 4-point strap for “hands-free” use
Continuity / Resistance:
I > 200 mA / 39.99 Ω / 0.01 Ω / ± (1.5% of the measurement + 2 cts) 12 mA / 39.99 Ω & 399 .9 Ω / 0.01 & 0.1 Ω /± (1.5 % of the measurement + 5 cts) with acoustic signal
Insulation:
Nominal voltage: Utest: 50 / 100 / 250 / 500 / 1000 VDC
Range / Resolution / Accuracy: 0.01 MΩ to 2 GΩ / 10 kΩ to 1 MΩ / ±(5% of measurement + 3 cts)
Short Circuit Current: ≤ 3 mA
Ground:
3P Ground: 0.50 Ω to 40 Ω / 0.01 Ω / ±(2% of measurement + 10 cts) • 40 Ω to 15 kΩ / 0.1 Ω to 1 Ω / ±(2 % of the measurement + 2 cts) 15 kΩ to 40 kΩ / 10 Ω / ±(10 % of the measurement + 2 cts)
Others: Resistance measurement of auxiliary probes RH & RS (up to 40kΩ)
Ufk: Meets SEV 3569
Selective 1P Ground: 0.20 Ω to 39.99 Ω - 40 Ω to 399.9 Ω / 0.01 Ω – 0.1 Ω / ±(10 % of the measurement + 10 cts) (ISel by clamp)
Loop impedance (Zi (L-PE) and Zs (L-N or L-L)) – GROUND WITH VOLTAGE 1P:
Live earth (Installation voltage / Frequency): 90 to 500 V / 15.8 a 17.5 Hz - 45 to 65 Hz
High current mode with trip (TRIP) Zs (L-PE) and Zi (L-N or L-L): Max. test current: 7.5 A (0.050) 0.100 Ω a 0.5 Ω / 0.001 Ω / ± (10% of measurement + 20 cts) • 0.5 Ω to 3.999 Ω / 0.001 Ω / ± (5% of measurement + 20 cts) 3.999 to 39.99 Ω / 0 .01 Ω / ± (5% of measurement + 2 cts) • 39.99 Ω to 399.99 Ω / 0.1 Ω / ± (5% of measurement + 2 cts)
Non-tripping mode (NO TRIP)n(only Zs (L-PE)): Test current: 6 mA – 9 mA – 12 mA (to choose) • 0.20 Ω to 0.99 Ω / 0.01 Ω / ± (15 % of the measure + 10 cts); 1.00 to 1.99 Ω / 0.01 Ω / ± (15% of measurement + 3 cts) • 2.00 to 39.99 Ω / 0.01Ω / ± (10% of measurement + 3 cts) 40.00 Ω to 399.9 Ω / 0.1 Ω / ± (5% of measurement + 2 cts) • 400 to 3999 Ω / 1 Ω / ± (5% of measurement + 2 cts)
Calculation of short circuit current; Ik (PFC (Zs)) , I Sc PSCC (Zi): Fault and short-circuit current: 0.1 A to 20 kA
Others: Others Measurement of the resistive and inductive components of impedances Zs and Zi
AC, A and F type differences:
Installation voltage / Frequency: 90 V to 500 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz
I ∆n: 6*/10/30/100/300/500/650/1000 mA (90 V - 280 V) or 6*/10/30/100/300/500 mA (280 V - 550 V) or variable / Ramp and pulse test
Non-trip test: at ½ I∆n – Duration: 1000 ms or 2000 ms
Ramp mode: 0.2 to 0.5 x I∆n (Uf) / 0 .3 x I∆n to 1.06 x I∆n in steps of 3.3 % x I∆n
Tripping time measurement: 0.2 to 0.5 x I∆n (Uf) / 0. 5 x I∆n / 2 x I∆n (selective) / 5 x I∆n ; Pulse: 0 to 500 ms / 0.1 and 1 ms / 2 ms, Ramp Mode: 0 to 200 ms / 0.1 ms / 2 ms
Other measurements:
Current via clamp current: 5.0 mA to 19.9 or 199.9 A (depending on the clamp)
Voltage: 0 to 550 AC/DC /DC and 15.8 to 500 Hz
Frequency: 10 to 500 Hz
Phase rotation: 20a 500 VAC
Display: Large monochrome graphic LCD screen 5.7” with backlight 320 x 240 dots
Autonomy: up to 24 hours
Dimensions / Weight: 280 x 190 x 128 mm / 2.2 kg
Protection index: IP 53 / IK04
EMC: IEC 61326-1
Electrical safety: IEC 61010 -1 – 600 V CAT III – 300 V CAT IV – IEC 61557