Advanced online protection for sensitive and critical cargo
This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
This 1500 VA, 1350 W online double-conversion uninterruptible power supply (UPS) is a tower-format unit with single-phase input and output, designed to protect servers, IT equipment, NAS storage systems, communications equipment, networks and other sensitive or critical loads. Its 0.9 output power factor supports loads whose active and apparent power remain within the unit’s rated limits.
AC-DC-AC double conversion supplies the loads from a pure sine wave PWM inverter, regulating the output voltage and reducing the effects of mains disturbances such as voltage and frequency fluctuations, power cuts and brief interruptions. With a compatible battery bank connected and available, the transition from inverter to battery supply has zero transfer time (0 ms) in online mode.
The B1 version incorporates an additional charger for 48 V DC external batteries. It is supplied without batteries or the corresponding battery bank connection accessories, which must be purchased separately. The nominal configuration of each string uses 4 12 V batteries in series; the manufacturer’s specified voltage, polarity, permissible capacity and protection requirements for the installation must be observed.
The additional charger current can be selected from 1.5 / 3 / 4.5 / 6 A, with a factory setting of 6 A according to the manual. Charging uses the I/U method (constant current/constant voltage). The number of connected external modules and charging current can be configured to suit the installed batteries. The module count setting must match the actual installation for the displayed runtime to be correct. Backup time and recharge time depend on battery bank configuration, capacity, state of charge, ageing and actual load consumption; no fixed backup time is assigned to the UPS supplied without batteries.
ECO mode improves efficiency by supplying the loads via the bypass when the mains meets the configured conditions. Continuous double conversion is not maintained in this mode and the return to the inverter has a different transfer time from online mode. The static bypass helps maintain the supply under permitted conditions, such as certain overloads; it is not a manual maintenance bypass.
The unit can also operate as a frequency converter (CVCF), with a 50 or 60 Hz output and power limited to 60% of the rated value. It features automatic input frequency detection, battery cold start when batteries are connected, automatic restart and an emergency power-off (EPO) function for the output.
The front LCD and keypad display input and output voltage and frequency, connected load level, battery status, operating modes, alarms and faults. They also allow parameter settings and manual or scheduled tests of the installed batteries.
The USB HID interface allows UPS monitoring and orderly computer shutdown using compatible systems and software. The manufacturer offers monitoring software for Windows, Linux, Unix and Mac. The intelligent slot accepts optional SNMP cards for network monitoring or relay signalling cards, neither of which is supplied as standard.
It has 2 Schuko sockets and 1 IEC C13 outlet. Installation protection, input and output connections and external battery bank sizing must comply with the unit’s rated characteristics. Temporary overload ratings must not be used to size the normal load. The battery bank must be connected by qualified personnel; the manufacturer recommends an initial charge of at least 12 hours before using the UPS with the installed batteries.
The unit has an IP20 rating, is intended for dry, ventilated indoor installations and operates from 0 to +40 °C. Power may be derated at high altitude. The B1 version allows a backup power solution to be tailored to extended runtime requirements without purchasing the internal batteries of a standard version.
| Equipment type | Online double-conversion UPS, B1 version without batteries |
| Format | Tower |
| Input / output | Single-phase / single-phase |
| Rated apparent power | 1500 VA |
| Rated active power | 1350 W |
| Rated input voltage | 220 / 230 / 240 V AC |
| Input range at 100% load | 176–300 V AC |
| Input range at 40% load | 100–300 V AC |
| Input frequency | 50 / 60 Hz, automatic detection |
| Input frequency range | ±10% (45–55 / 54–66 Hz) |
| Input power factor | ≥ 0.99 |
| Input current harmonic distortion (THDi) | < 3.5% |
| Input protection | Resettable circuit breaker |
| Rated output voltage | 220 / 230 / 240 V AC |
| Output power factor | 0.9 |
| Output waveform | Pure sine wave |
| Voltage accuracy in battery mode | ±1% |
| Voltage harmonic distortion (THDv) | < 2% linear load / < 5% non-linear load |
| Output frequency with mains | 50 / 60 Hz, synchronised within ±10% |
| Output frequency without mains | 50 / 60 Hz ±0.05 Hz |
| Frequency synchronisation slew rate | 1 Hz/s |
| Crest factor | 3:1 |
| APFC load compatibility | Yes |
| Online transfer to battery | 0 ms (with compatible battery bank available) |
| Inverter-to-bypass transfer | < 4 ms |
| ECO-to-inverter transfer | < 10 ms |
| Full-load online efficiency (manual) | > 91% with fully charged batteries |
| Full-load ECO efficiency (manual) | > 98% |
| Permissible overload in line mode | Up to 105% continuous / 130% 60 s / 150% 10 s / > 150% 300 ms |
| Permissible overload in battery mode | Up to 105% continuous / 130% 10 s / 150% 1 s |
| Permissible overload in bypass mode | Up to 130% continuous / 180% 60 s |
| Bypass frequency range | ±5 Hz |
| Output sockets | 2 Schuko sockets and 1 IEC C13 outlet |
| Batteries included | No; external bank required to provide backup runtime |
| Specified battery type | Sealed lead-calcium (Pb-Ca), AGM, maintenance-free |
| Rated external battery bank voltage | 48 V DC |
| 12 V batteries per string | 4 in series |
| Battery bank float voltage | 54.6 V DC |
| B1 additional charger | 1.5 / 3 / 4.5 / 6 A, selectable (factory setting 6 A) |
| Charging method | I/U (constant current / constant voltage) |
| Charging temperature compensation | −20 mV/°C per 12 V battery from 25 °C |
| Backup runtime and recharge time | Depend on external bank, configuration and load; not defined for the unit without batteries |
| Recommended initial charge | At least 12 h with batteries installed |
| External battery connection | Polarised connector; compatible external modules, not included |
| External module count setting | 0–9; set to the actual number of modules according to the manual |
| Protection between UPS and battery bank (manual table 2) | 125 V DC / 40 A |
| Battery test | Manual and/or programmable automatic |
| Operating modes | Online, battery, bypass, ECO, frequency converter |
| Frequency converter mode | 50 / 60 Hz; up to 60% of rated power |
| Battery cold start | Yes, with batteries connected |
| Automatic restart / EPO | Yes / Yes |
| Control panel | LCD and keypad |
| Communication port | USB HID |
| Intelligent slot | Optional SNMP or relay card |
| Monitoring software | Windows, Linux, Unix and Mac; subject to software compatibility |
| Operating temperature | 0 to +40 °C |
| Storage temperature without batteries | −20 to +70 °C |
| Relative humidity | 0–95%, non-condensing |
| Operating altitude | 2400 m; derated power up to 5000 m |
| Acoustic noise at 1 m | ≤ 49 dB at 100% load / ≤ 41 dB at 60% |
| IP rating | IP20 |
| B1 UPS dimensions (depth × width × height) | 390 × 102 × 327 mm |
| B1 UPS weight without batteries | 6.4 kg |
| Safety standard | EN-IEC 62040-1 |
| Electromagnetic compatibility | EN 62040-2 |
| Performance classification | VFI-SS-11 (EN 62040-3) |
| EAN-13 | 8436035921720 |