This 63 A manual maintenance bypass allows a single-phase uninterruptible power supply (UPS) to be isolated for servicing, repair or replacement while the loads remain powered directly from the mains. Its advanced functions are designed for integration with compatible SLC TWIN RT3 and SLC TWIN PRO3 units.
Transfer between the UPS and mains is performed using a make-before-break manual selector switch. The RJ45 detection link allows a compatible UPS to enter static bypass automatically when the selector lock is removed. Changeover must be carried out with the UPS in bypass mode and in the sequence specified by the manufacturer.
The unit provides six IEC outlets, comprising two IEC C19 and four IEC C13 outlets arranged as two banks of three. One bank remains permanently available and the other can be programmed through the UPS. The programmable bank can be set to remain on continuously or to switch off automatically when battery capacity falls below 50%, then switch back on when the charger starts.
Two RJ45 ports maintain the detection link between the UPS and an external battery module (EBM). This allows the system to continue detecting the battery module when the bypass is installed between the two units.
The mounting supports allow installation in a 19-inch rack, attachment to the UPS or rotation of the bypass for servicing without complete removal. Power wiring uses terminal blocks with a recommended cable cross-section of 10 mm². Installation must be carried out by qualified electrical personnel, with the protective earth connected before the supply and with a recommended output cable length not exceeding 10 m.
| Manufacturer part number | 6B4OP000002 |
| Type | Manual maintenance bypass |
| Application | Compatible single-phase UPS systems |
| Advanced functional compatibility | SLC TWIN RT3 / SLC TWIN PRO3 |
| Input/output configuration | Single-phase / single-phase |
| Changeover | Manual, UPS-to-mains and mains-to-UPS |
| Switch type | Make-before-break |
| Transfer control | Via RJ45 detection link with a compatible UPS |
| Installation format | 19-inch rack / wall-mounted / attached to equipment |
| Service support | Rotating and fold-down |
| Rated input voltage | 208 / 220 / 230 / 240 V |
| Rated input frequency | 50 / 60 Hz |
| Rated input current | 63 A |
| Rated output voltage | 208 / 220 / 230 / 240 V |
| Rated output frequency | 50 / 60 Hz |
| Rated output current | 63 A |
| Mains input | Terminals |
| Connection to UPS input | Terminals |
| Connection from UPS output | Terminals |
| Terminal load output | Terminals |
| IEC outlets | 2 × IEC C19 + 4 × IEC C13 |
| IEC outlet arrangement | 2 banks of 3 outlets |
| Outlet bank 1 | Non-programmable |
| Outlet bank 2 | Programmable |
| Programmable bank modes | Always on / automatic shutdown |
| Automatic shutdown threshold | Battery capacity below 50% |
| Programmable bank reactivation | When the charger starts |
| Detection ports | 2 × RJ45 for UPS and EBM |
| Battery module detection | Via UPS-BM-R-EBM RJ45 link |
| Recommended cable cross-section | 10 mm² |
| Recommended maximum output cable length | 10 m |
| Input circuit breaker | 100 A, 400/415 V AC |
| Protective earth connection | Required before connecting the supply |
| Ingress protection rating | IP20 |
| Operating temperature | 0–45 °C |
| Relative humidity | Up to 95%, non-condensing |
| Maximum operating altitude | 2,400 m |
| Safety standard | EN IEC 62040-1 |
| Dimensions (depth × width × height) | 80 × 440 × 85 mm |
| Weight | 2.4 kg |