This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-6000-TWIN RT3 B1 is a 6000 VA / 6000 W On-line double-conversion UPS with unity output power factor, designed for installations requiring protected power and scalable backup capacity using external batteries. The B1 version has no internal batteries and batteries cannot be installed inside the UPS chassis; an uprated charger adjustable up to 12 A is provided.
Double-conversion operation continuously supplies connected loads through the inverter and provides a pure sine-wave output, isolating equipment from voltage and frequency variations, electrical noise, outages and short interruptions. Input power factor is ≥0.99 and THDi is ≤5% at full load.
The compact 2U unit supports 19-inch rack or tower installation. Main input and output are hardwired and two auxiliary 10 A IEC C13 outlets are also provided. An included PDU adds six IEC C13 and two IEC C19 outlets for load distribution.
The external battery system operates at 192 V DC and supports up to six EBM modules. Modules are automatically detected through an RJ45 communication connection and charging current can be adjusted from 0 to 12 A, with a 4 A default setting.
Connectivity includes USB-HID, RS-232 and RJ45 Ethernet for NIMBUS Cloud, an HDMI port for the optional WLAN dongle and an intelligent slot for SNMP, potential-free contacts or MODBUS. Programmable digital I/O, remote emergency power-off, ECO mode and frequency-converter operation are also provided.
Typical applications include servers, storage systems, networking equipment, voice and data networks, ERP and CRM systems, document management and other critical IT loads. Up to three units can operate in parallel using the corresponding optional kit.
| Electrónica Embajadores reference | SA81RC08 |
| Salicru model | SLC-6000-TWIN RT3 B1 |
| Salicru reference | 6B4AB000006 |
| Configuration | B1, uprated external-battery charger, no internal batteries |
| Technology | On-line double conversion, PFC and dual DC bus |
| Input / output topology | Single-phase / single-phase |
| Format | Convertible tower / rack, 2U |
| Power rating | 6000 VA / 6000 W |
| Output power factor | 1 |
| Rated input voltage | 220 / 230 / 240 V AC |
| Input voltage range | 110–300 V AC; load derating down to 50% at low input voltage |
| Rated input frequency | 50 / 60 Hz, auto-detect |
| Input frequency range | 50 ±10 Hz / 60 ±10 Hz |
| THDi | ≤5% at full load |
| Input power factor | ≥0.99 at full load |
| Recommended input protection | 63 A curve D circuit breaker |
| Output waveform | Pure sine wave |
| Rated output voltage | 220 / 230 / 240 V AC |
| Output voltage accuracy in battery mode | ±1% |
| THDv | <1% with linear load; <5% with non-linear load |
| Synchronised frequency | 50 ±5 Hz / 60 ±6 Hz |
| Maximum crest factor | 3:1 |
| Line ↔ battery transfer time | 0 ms |
| Line ↔ bypass transfer time | 0 ms |
| ECO ↔ inverter transfer time | 10 ms |
| On-line efficiency | 95% |
| ECO-mode efficiency | 98% |
| Main input / output connection | Terminal block |
| Auxiliary outputs | 2 × IEC C13, 10 A |
| Included PDU | 6 × IEC C13 + 2 × IEC C19 |
| PDU supply input | IEC C20 |
| Parallel operation | Up to 3 units with optional kit |
| Internal batteries | No |
| External battery type | Sealed maintenance-free Pb-Ca AGM |
| Battery-system voltage | 192 V DC |
| Configurable battery capacity | Up to 300 Ah |
| Maximum EBM modules | 6 |
| Automatic EBM detection | Yes |
| Battery management | Optimised Battery Management (OBM) |
| Default charging current | 4 A |
| Adjustable charging current | 0–12 A |
| Recharge time | Depends on the external battery configuration and capacity |
| Communication | USB-HID, RS-232 and RJ45 Ethernet |
| Wireless connectivity | Optional WLAN dongle connected to the HDMI port |
| Intelligent slot | SNMP / potential-free contacts / MODBUS |
| Remote management | NIMBUS Cloud, mobile app and web portal |
| Digital I/O | 1 programmable Dry In + 1 programmable Dry Out |
| RPO / EPO | Yes |
| Cold Start | Yes, with batteries connected |
| ECO mode | Yes |
| Frequency converter | Yes, with or without batteries; power derated to 60% |
| Control panel | Rotatable Dot Matrix display and keypad |
| Protection rating | IP20 |
| Operating temperature | 0–50 °C; power derating between 40 and 50 °C |
| UPS storage temperature without batteries | −25–55 °C |
| Relative humidity | 0–95%, non-condensing |
| Operating altitude without derating | Up to 2400 m |
| Altitude derating | 1% per 100 m from 2400 to 5000 m |
| Dimensions (depth × width × height) | 570 × 438 × 86 mm |
| Front rack projection | 35 mm in addition to the stated depth |
| Rack height | 2U |
| Weight | 13.6 kg |
| Rack rails | Included |
| Safety | EN IEC 62040-1 |
| Electromagnetic compatibility | EN 62040-2, category C3 |
| Performance classification | VFI-SS-11, EN 62040-3 |