Model without batteries. Requires external battery module
This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-3000-TWIN RT3 B1 is a 3000 VA / 3000 W On-line double-conversion UPS module with unity output power factor, designed for operation with an external battery system. The B1 version is supplied without internal batteries and batteries cannot be installed inside its chassis; an uprated 8 A charger is provided for extended-runtime configurations.
Double-conversion operation continuously powers connected loads through the inverter, providing a pure sine-wave output and protection against voltage and frequency variations, electrical noise, outages and short interruptions.
The 2U format converts between 19-inch rack and tower installation. Eight 10 A IEC C13 outputs are divided into four main and four programmable outlets, while an additional non-programmable 16 A IEC C19 outlet can supply a higher-power load. The input connector is IEC C20.
The battery system operates at 72 V DC and supports up to four external EBM modules with automatic detection. Charging current can be set to 2, 4, 6 or 8 A. As no internal batteries are fitted, an external battery system is required to provide backup runtime during a mains outage.
Connectivity includes USB-HID, RS-232, RJ45 Ethernet for NIMBUS Cloud, HDMI for the optional WLAN dongle and an intelligent slot for SNMP, AS400 or MODBUS.
| Electrónica Embajadores reference | SA81RC06 |
| Salicru model | SLC-3000-TWIN RT3 B1 |
| Salicru reference | 6B4AA000006 |
| Configuration | B1, uprated external-battery charger, no internal batteries |
| Technology | On-line double conversion |
| Topology | Single-phase / single-phase |
| Format | Convertible tower / rack, 2U |
| Power rating | 3000 VA / 3000 W |
| Output power factor | 1 |
| Rated input voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Input voltage range | 160–300 V AC; 110–160 V AC with linear load derating to 50% |
| Input frequency | 50 / 60 Hz, auto-detect |
| THDi | ≤5% |
| Input power factor | ≥0.99 |
| Input connector | IEC C20 |
| Output waveform | Pure sine wave |
| Rated output voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Output accuracy | ±1% |
| THDv | <1% linear load; <5% non-linear load |
| IEC C13 outputs | 8 × IEC C13, 10 A |
| IEC C13 arrangement | 4 main + 4 programmable outlets |
| Additional output | 1 × IEC C19, 16 A, non-programmable |
| Internal batteries | Not included; cannot be installed inside the UPS chassis |
| External battery type | Sealed maintenance-free Pb-Ca AGM |
| Battery-system voltage | 72 V DC |
| Maximum EBM modules | 4 |
| Charging current | 8 A; selectable 2 / 4 / 6 / 8 A |
| Recharge time | Depends on the external battery configuration |
| Communication | USB-HID, RS-232, RJ45 Ethernet and HDMI |
| Intelligent slot | SNMP / AS400 / MODBUS |
| NIMBUS Cloud | Yes |
| RPO / EPO | Yes |
| Cold Start | Yes, with batteries connected |
| ECO mode | Yes |
| Frequency converter | Yes; power derated to 60% |
| Display | Rotatable Dot Matrix display |
| Operating temperature | 0–50 °C; 4% power derating per degree above 40 °C |
| Relative humidity | Up to 95%, non-condensing |
| Maximum altitude without derating | 2400 m |
| Dimensions | 570 × 438 × 86 mm |
| Rack height | 2U |
| Weight | 10.7 kg |
| Safety | EN IEC 62040-1 |
| Electromagnetic compatibility | EN IEC 62040-2, category C2 |
| Performance classification | VFI-SS-31, EN 62040-3 |