Model without batteries. Requires external battery module
This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-1500-TWIN RT3 B1 is a 1500 VA / 1500 W On-line double-conversion UPS module with unity output power factor, designed for use with external batteries. The B1 version contains no internal battery pack and batteries cannot be installed inside the UPS chassis; instead, it features an uprated 8 A charger for extended-runtime configurations.
Double-conversion technology continuously supplies connected loads through the inverter, providing a pure sine-wave output and isolating equipment from mains voltage and frequency variations, electrical noise, outages and short interruptions.
The 2U unit can be installed in a 19-inch rack or vertically as a tower. It provides eight 10 A IEC C13 outputs, divided into four main outlets and four programmable outlets for separate management of critical and non-critical loads. The input connector is IEC C14.
The battery system operates at 36 V DC and supports up to four external EBM modules with automatic detection. Charging current can be set to 2, 4, 6 or 8 A. Without an external battery system connected, the unit does not provide backup runtime during a mains failure.
Connectivity includes USB-HID, RS-232 and RJ45 Ethernet for NIMBUS Cloud, plus an HDMI port for the optional WLAN dongle and an intelligent slot for SNMP, AS400 or MODBUS.
| Electrónica Embajadores reference | SA81RC05 |
| Salicru model | SLC-1500-TWIN RT3 B1 |
| Salicru reference | 6B4AA000005 |
| Configuration | B1, uprated external-battery charger, no internal batteries |
| Technology | On-line double conversion |
| Input / output topology | Single-phase / single-phase |
| Format | Convertible tower / rack, 2U |
| Power rating | 1500 VA / 1500 W |
| Output power factor | 1 |
| Rated input voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Input voltage range | 160–300 V AC; 110–160 V AC with linear load derating to 50% |
| Rated input frequency | 50 / 60 Hz, auto-detect |
| THDi | ≤5% |
| Input power factor | ≥0.99 |
| Input connector | IEC C14 |
| Output waveform | Pure sine wave |
| Rated output voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Output voltage accuracy | ±1% |
| THDv | <1% with linear load; <5% with non-linear load |
| Outputs | 8 × IEC C13, 10 A |
| Output arrangement | 4 main + 4 programmable outlets |
| Internal batteries | Not included; cannot be installed inside the UPS chassis |
| External battery type | Sealed maintenance-free Pb-Ca AGM |
| Battery-system voltage | 36 V DC |
| Maximum EBM modules | 4 |
| Charging current | 8 A; selectable 2 / 4 / 6 / 8 A |
| Recharge time | Depends on the external battery configuration |
| Communication | USB-HID, RS-232, RJ45 Ethernet and HDMI |
| Intelligent slot | SNMP / AS400 / MODBUS |
| NIMBUS Cloud | Yes |
| RPO / EPO | Yes |
| Cold Start | Yes, with batteries connected |
| ECO mode | Yes |
| Frequency converter | Yes; power derated to 60% |
| Display | Rotatable Dot Matrix display |
| Operating temperature | 0–50 °C; 4% power derating per degree above 40 °C |
| Relative humidity | Up to 95%, non-condensing |
| Maximum altitude without derating | 2400 m |
| Dimensions | 570 × 438 × 86 mm |
| Rack height | 2U |
| Weight | 8.1 kg |
| Safety | EN IEC 62040-1 |
| Electromagnetic compatibility | EN IEC 62040-2, category C2 |
| Performance classification | VFI-SS-31, EN 62040-3 |