This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-4000-TWIN RT3 is a 4000 VA / 4000 W On-line double-conversion UPS with unity output power factor for servers, voice and data networks, ERP and CRM systems, storage, document management and other critical IT loads.
Double-conversion operation provides a continuous pure sine-wave output. The unit features an input power factor of ≥0.99, THDi ≤5%, ±1% output regulation and 0 ms transfer time between line and battery operation. Efficiency reaches 95% in On-line mode and 98% in ECO mode.
The system converts between tower and rack installation. The UPS occupies 2U and the standard backup configuration uses a 3U EBM battery module. Main input and output are hardwired, with two auxiliary IEC C13 outlets. An included PDU provides six IEC C13 and two IEC C19 outlets.
The battery module uses sixteen 12 V / 7 Ah sealed Pb-Ca AGM batteries for a nominal 192 V DC system. Up to six EBM modules are supported.
USB-HID, RS-232, Ethernet for NIMBUS Cloud, digital I/O, EPO and an intelligent slot for SNMP, potential-free contacts or MODBUS are provided. Up to three UPS units can operate in parallel with the optional parallel kit.
| Electrónica Embajadores reference | SA81R400 |
| Salicru model | SLC-4000-TWIN RT3 |
| Salicru reference | 6B4AC000001 |
| Technology | On-line double conversion |
| Topology | Single-phase / single-phase |
| Format | Tower / rack; 2U UPS + 3U EBM |
| Power rating | 4000 VA / 4000 W |
| Output power factor | 1 |
| Rated input voltage | 220 / 230 / 240 V AC |
| Input voltage range | 160–300 V AC; down to 110 V AC at 50% load |
| Rated frequency | 50 / 60 Hz, auto-detect |
| THDi | ≤5% |
| Input power factor | ≥0.99 |
| Output waveform | Pure sine wave |
| Rated output voltage | 220 / 230 / 240 V AC |
| Voltage accuracy | ±1% |
| THDv | <1% linear load; <5% non-linear load |
| Line / battery transfer time | 0 ms |
| On-line efficiency | 95% |
| ECO-mode efficiency | 98% |
| Main input / output connection | Terminal block |
| Auxiliary outputs | 2 × IEC C13, 10 A |
| Included PDU | 6 × IEC C13 + 2 × IEC C19 |
| Parallel operation | Up to 3 units with optional kit |
| Battery type | Sealed Pb-Ca AGM, maintenance-free |
| Battery system voltage | 192 V DC |
| Standard battery configuration | 16 × 12 V / 7 Ah |
| Recharge time | 3 h to 90% |
| Charging current | 1.4 A default; adjustable 0–4 A |
| Maximum EBM modules | 6 |
| Communication | USB-HID, RS-232, RJ45 Ethernet and HDMI |
| Intelligent slot | SNMP / potential-free contacts / MODBUS |
| EPO / RPO | Yes |
| NIMBUS Cloud | Yes |
| ECO mode | Yes |
| Frequency converter | Yes; power derated to 60% |
| Protection rating | IP20 |
| Operating temperature | 0–50 °C |
| Relative humidity | 0–95%, non-condensing |
| Operating altitude | 2400 m |
| Standard-system dimensions | 592 × 438 × 220 mm |
| Standard-system weight | 55.6 kg |
| Standards | EN IEC 62040-1; EN 62040-2 C3; VFI-SS-11 (EN 62040-3) |