This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-10000-TWIN RT3 is a 10 kVA / 10 kW On-line double-conversion UPS with unity output power factor for high-power critical loads in data centres, servers, storage, communications, ERP/CRM systems and other IT infrastructure.
On-line architecture continuously supplies the load through the inverter with a pure sine-wave output, ±1% voltage regulation and 0 ms transfer between mains and battery. The input incorporates PFC with a power factor of ≥0.99 and THDi ≤5%. Efficiency is 95% On-line and 98% in ECO mode.
The system can be installed in rack or tower configuration. The UPS occupies 2U and the standard battery module 3U. Main power input and output are hardwired. Two IEC C13 outputs and an included PDU with six IEC C13 and two IEC C19 outlets are also provided.
Standard backup uses sixteen 12 V / 9 Ah sealed Pb-Ca AGM batteries at a nominal 192 V DC. Charging current is 2 A by default, adjustable from 0 to 4 A, and up to six EBM modules are supported.
Ethernet for NIMBUS Cloud, USB-HID, RS-232, digital I/O and an intelligent SNMP/potential-free-contact/MODBUS slot provide integration with management systems. EPO, ECO mode, frequency-converter operation and parallel operation of up to three units are also available.
| Electrónica Embajadores reference | SA81R10K |
| Salicru model | SLC-10000-TWIN RT3 |
| Salicru reference | 6B4AC000005 |
| Technology | On-line double conversion, PFC |
| Topology | Single-phase / single-phase |
| Format | Tower / rack; 2U UPS + 3U EBM |
| Power rating | 10000 VA / 10000 W |
| Output power factor | 1 |
| Rated input voltage | 220 / 230 / 240 V AC |
| Input voltage range | 160–300 V AC; down to 110 V AC at 50% load |
| Rated frequency | 50 / 60 Hz, auto-detect |
| THDi | ≤5% |
| Input power factor | ≥0.99 |
| Output waveform | Pure sine wave |
| Rated output voltage | 220 / 230 / 240 V AC |
| Output accuracy | ±1% |
| THDv | <1% linear load; <5% non-linear load |
| Line / battery transfer time | 0 ms |
| On-line efficiency | 95% |
| ECO-mode efficiency | 98% |
| Main input / output | Terminal block |
| Auxiliary outputs | 2 × IEC C13, 10 A |
| Included PDU | 6 × IEC C13 + 2 × IEC C19 |
| Parallel operation | Up to 3 units with optional kit |
| Recommended input protection | 100 A, curve D |
| Battery type | Sealed Pb-Ca AGM, maintenance-free |
| Battery voltage | 192 V DC |
| Standard configuration | 16 × 12 V / 9 Ah |
| Recharge time | 3 h to 90% |
| Charging current | 2 A default; adjustable 0–4 A |
| Maximum EBM modules | 6 |
| Communication | USB-HID, RS-232, RJ45 Ethernet and HDMI |
| Intelligent slot | SNMP / potential-free contacts / MODBUS |
| Dry In / Dry Out | Programmable |
| EPO / RPO | Yes |
| NIMBUS Cloud | Yes |
| ECO mode | Yes |
| Frequency converter | Yes; power derated to 60% |
| Control panel | Rotatable multilingual Dot Matrix display |
| Protection rating | IP20 |
| Operating temperature | 0–50 °C |
| Storage temperature with battery | −15–40 °C |
| Relative humidity | 0–95%, non-condensing |
| Maximum operating altitude without stated derating | 2400 m |
| Standard-backup system dimensions | 592 × 438 × 220 mm |
| Standard-backup system weight | 64.5 kg |
| Rack rails | Included |
| Standards | EN IEC 62040-1; EN 62040-2 C3; VFI-SS-11 (EN 62040-3) |