This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
The SALICRU SLC-2000-TWIN RT2 LION is a 2000 VA / 1800 W On-line double-conversion UPS for continuous protection of critical electronic loads. Its rectifier-inverter architecture provides a pure sine-wave output independent of mains disturbances and eliminates battery transfer delay, providing a 0 ms transfer time.
The input incorporates power factor correction with a value of ≥0.99 at full load and THDi of ≤5%. Its wide input range allows operation to continue without using the battery during a broad range of mains variations. ECO mode and configurable frequency-converter operation are also provided.
This model uses two LiFePO₄ LiFe-48500 batteries connected in parallel. Each module is rated at 48 V / 5 Ah, providing a total battery-group capacity of 10 Ah. Lithium-ion technology provides more than 2000 discharge cycles according to the series documentation and a high capacity-to-weight and capacity-to-volume ratio.
The convertible 2U format supports tower or 19-inch rack installation. Tower supports and rack ears are supplied, while the front LCD can be rotated to suit the selected orientation. Internal rack rails are optional.
Eight 10 A IEC C13 outputs are divided into four outputs for critical loads and four programmable outputs for non-critical loads. The input uses a 16 A IEC C20 connector appropriate for the higher power rating of this model.
Communications include USB-HID, RS-232 and an intelligent slot for optional relay, SNMP or RS485 Modbus cards. EPO and RJ45 communication-line protection are also provided.
It is intended for servers, storage, communication networks, edge infrastructure, CAD/CAM applications, streaming systems and other IT installations where continuity and power quality are critical.
| Electrónica Embajadores reference | SA81LI200 |
| Salicru model | SLC-2000-TWIN RT2 LION |
| Salicru reference | 698LA000003 |
| Technology | On-line double conversion, PFC and dual DC bus |
| Input / output topology | Single-phase / single-phase |
| Format | Convertible tower / rack, 2U |
| Power rating | 2000 VA / 1800 W |
| Rated input voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Input voltage range | 160–300 V AC at 100% load; down to 110 V AC at ≤60% load |
| Input frequency | 50 / 60 Hz, auto-detect |
| Input frequency range | ±10 Hz; 40–60 Hz / 50–70 Hz |
| Input harmonic distortion (THDi) | ≤5% at full load |
| Input power factor | ≥0.99 at full load |
| Output waveform | Pure sine wave |
| Output power factor | 0.9 |
| Rated output voltage | 200 / 208 / 220 / 230 / 240 V AC |
| Power derating at 200 / 208 V | 90% of rated power |
| Output voltage accuracy | ±1% |
| Output harmonic distortion (THDv) | ≤2% with linear load; <4% with non-linear load |
| Output frequency with mains present | Synchronised, 47–53 Hz / 57–63 Hz |
| Output frequency in battery mode | 50 / 60 Hz ±0.1 Hz |
| Inverter / battery transfer time | 0 ms |
| Full-load On-line efficiency | >91% |
| ECO-mode efficiency | >96% |
| Crest factor | 3:1 |
| Static bypass | Yes |
| Programmable outputs | Yes; 4 critical loads + 4 programmable/non-critical loads |
| Battery type | LiFePO₄ |
| Battery model and configuration | LiFe-48500 × 2 in parallel |
| Voltage / capacity per battery | 48 V / 5 Ah |
| Total battery-group capacity | 10 Ah |
| End-of-backup cut-off voltage | 39.8 V DC |
| Discharge cycles | >2000 |
| Charger voltage | 52.5 V DC |
| Charging current | 1 / 2 / 4 / 6 / 8 A; 4 A default |
| Recharge time | Up to 3 h to 100% |
| Input connector | IEC C20, 16 A |
| Output connectors | 8 × IEC C13, 10 A |
| Communication ports | USB-HID and RS-232 DB9, mutually exclusive operation |
| Intelligent slot | Yes; optional relay, SNMP or RS485 Modbus cards |
| Monitoring software | ViewPower |
| Operating systems | Windows, Linux and Mac |
| Data-line protection | ADSL / fax / modem via RJ45 |
| Cold Start | Yes |
| EPO emergency power off | Yes |
| ECO mode | Yes |
| Frequency converter | Yes |
| Control panel | Rotatable LCD and keypad |
| Protection rating | IP20 |
| Operating temperature | 0–40 °C |
| Storage temperature | −15–50 °C |
| Relative humidity | 0–95%, non-condensing |
| Maximum operating altitude | 2400 m; power derating up to 5000 m |
| Acoustic noise at 1 m | <50 dB |
| Dimensions (depth × width × height) | 510 × 438 × 88 mm |
| Front projection in rack installation | 35 mm additional to stated depth |
| Rack height | 2U |
| Weight | 15.2 kg |
| Safety | EN-IEC 62040-1 |
| Electromagnetic compatibility | EN-IEC 62040-2, category C2 |
| Performance classification | EN-IEC 62040-3, VFI-SS-11 |