Sold out. We can let you know when it is available.
NYCY 0.6/1 kV shielded power and control cable with three 1.5 mm² insulated conductors and a 1.5 mm² concentric copper conductor. It is primarily intended for industrial environments where a degree of electromagnetic protection is required.
Construction comprises bare-copper conductors, PVC insulation, PVC bedding, a concentric conductor made from copper wires with counter-helical copper tape, and a black UV-resistant PVC outer sheath.
For three-conductor configurations, the manufacturer particularly recommends it for connecting variable-frequency drives. It is also suitable for indoor and outdoor installation, dry or humid locations, installation in air, or direct burial with suitable sand backfilling.
The concentric conductor acts as a screen and, where permitted by the regulations applicable to the installation, may also be used as a neutral or protective/earth conductor. This reference is a 3X configuration with brown, black and grey insulated conductors; it is not a 3G construction with an insulated green/yellow conductor.
Operating voltage is 600/1000 V and test voltage is 4000 V. For manufacturer code 28580700, Cervi specifies an approximate outer diameter of 13.2 mm, cable weight of 220 kg/km and conductor resistance of 12.1 Ω/km at 20 °C.
Stated maximum current is 19 A in air at 30 °C and 27 A underground at 20 °C. These figures depend on the installation conditions defined by the manufacturer and should not be treated as universal limits for every installation.
The cable is built to VDE 0276-603, has CPR class Eca according to UNE-EN 50575 and is flame-retardant according to VDE 0482-332-1-2 / IEC 60332-1-2. This Electrónica Embajadores reference is sold as a 50 m roll.
| Electrónica Embajadores reference | CA2A220 |
| Brand | Cervi |
| Manufacturer reference | 28580700 |
| Manufacturer family / designation | CERVIWIRE NYCY 0.6/1 kV CPR |
| Type | Shielded power and control cable |
| Configuration | 3 × 1.5 mm² + 1.5 mm² concentric conductor |
| Manufacturer configuration code | 3X1.5/1.5 |
| Main insulated conductors | 3 |
| Main conductor cross-section | 1.5 mm² |
| Concentric conductor / screen cross-section | 1.5 mm² |
| Conductor material | Bare copper |
| Conductor class for this size | Class I |
| Insulation | PVC |
| Bedding | PVC |
| Screen / concentric conductor | Concentric copper wires + counter-helical copper tape |
| Outer sheath | UV-resistant PVC |
| Sheath colour | Black |
| Insulated conductor colours | Brown, black and grey |
| Operating voltage | 0.6/1 kV — 600/1000 V |
| Test voltage | 4000 V |
| Stated operating temperature | −5 to +70 °C |
| Approximate outer diameter | 13.2 mm |
| Approximate cable weight | 220 kg/km |
| Conductor resistance at 20 °C | 12.1 Ω/km |
| Maximum current in air | 19 A at 30 °C |
| Maximum current underground | 27 A at 20 °C |
| Minimum bending radius, fixed installation | 158 mm |
| Maximum installation tensile load | 225 N |
| Reference standard | VDE 0276-603 |
| CPR classification | Eca according to UNE-EN 50575 |
| Flame behaviour | Flame-retardant according to VDE 0482-332-1-2 / IEC 60332-1-2 |
| UV resistance | Yes |
| Installation | Indoor/outdoor; dry or humid locations; in air or buried with suitable sand backfilling |
| Highlighted application | Industrial environments and variable-frequency-drive connections |
| Commercial presentation | 50 m roll |