Battery not in stock. Usual Term: 2-3 days
This product is not currently in stock in our store. However, it can still be purchased and will be shipped directly from the manufacturer.
Yuasa NP65-12I is a rechargeable valve-regulated lead-acid (VRLA) battery using AGM technology, intended for backup power applications and compatible equipment. Its nominal voltage is 12 V and its stated capacity is 65 Ah.
The electrolyte is absorbed in glass-fibre separators and does not require periodic water topping-up. The battery contains 6 cells connected in series.
Runtime depends on the connected load, temperature and the equipment's minimum operating voltage. The specified maximum discharge current is 800 A for 1 second and 500 A for 1 minute. The stated maximum discharge currents apply to short intervals and are not permissible continuous discharge currents.
Connection uses M6 hembra terminals. Before replacement, check the voltage, dimensions, terminals, polarity and equipment's charging requirements.
Use a charger compatible with VRLA lead-acid batteries and observe terminal polarity. Avoid short circuits, overcharging and ignition sources; do not install the battery in an unventilated sealed enclosure. At end of life, take it to an authorised lead-acid battery collection facility.
Yuasa maximum current ratings apply to short discharges (1 second and 1 minute); they are not permissible continuous operating currents.
The stated dimensions are 350 × 166 × 174 mm. The stated approximate weight is 21.4 kg.
For correct interpretation of the capacity rating: 20 h to 1.75 V/cell at 20 °C. The stated approximate internal resistance is 5 mΩ. The specified charging current limit is 16.25 A. The stated float charging voltage is 13.65 V at 20 °C. The stated cyclic charging voltage is 14.5 V at 20 °C.
| Manufacturer | Yuasa |
| Retail reference | BA11NP6512 |
| Model | NP65-12I |
| Technology | Lead-acid VRLA-AGM |
| Nominal voltage | 12 V |
| Number of cells | 6 |
| Nominal capacity | 65 Ah |
| Maximum discharge current (1 s) | 800 A |
| Maximum discharge current (1 min) | 500 A |
| Charge current limit | 16,25 A |
| Terminals | M6 hembra |
| Dimensions (L × W × H) | 350 × 166 × 174 mm |
| Capacity at 10 h | 60,5 Ah |
| Approximate internal resistance | 5 mΩ |
| Approximate weight | 21,4 kg |
| Typical constant power (10 min) | 1401,18 W en 10 min, to 9,6 V at 20 °C |
| Declared capacity rating conditions | 20 h, to 1,75 V/cell at 20 °C |
| Float charging voltage | 13,65 V at 20 °C |
| Cyclic charging voltage | 14,5 V at 20 °C |