Portable combustible-gas detector for methane, propane and isobutane, designed to locate and monitor gas concentrations in difficult-to-reach areas using an approximately 36 cm flexible probe. The colour display shows detected gas concentration together with ambient temperature and humidity in real time.
For methane, the documented range is 0 to 50,000 ppm, and concentration can also be displayed as %LEL over a 0 to 100% LEL range. Stated resolution is 1 ppm / 1% LEL. The manufacturer does not publish a numerical measurement accuracy in the reviewed documentation, so no unspecified metrological accuracy is attributed.
After power-on, the detector requires approximately 15–16 s warm-up. Once ready, it responds quickly to changes in gas concentration: it reaches approximately 90% of the final reading in under 5 s and, when the gas is removed, the indication falls to approximately 10% in under 10 s. Sampling time is approximately 0.5 s, and stated sensor service life is more than 3 years.
High and low thresholds are configurable. When exceeded, the unit can warn through an indicator light, vibration and buzzer. The alarm log stores up to 30 events with date, time and type; once this capacity is exceeded, the manual states that previous entries are cleared and a new cycle begins.
HOLD freezes the current reading, while the curve display helps track concentration changes with a 0.5 s refresh. The detector also includes a torch for low-light areas, light and dark interface themes, brightness adjustment, date and time, volume, sleep mode, automatic power-off and factory reset.
The GD-02 uses a 2.0-inch colour display and supports Simplified Chinese and English. Firmware can also be updated through USB-C and Bootloader mode. FNIRSI lists the detector, USB-C charging cable, storage case, user manual and packaging box as supplied items.
The sensor requires specific care: keep it away from vapours of volatile silicone compounds, high concentrations of corrosive gases, alkalis, alkali salts, halogens and liquids. Do not spray lighter gas directly onto the sensor or leave it for prolonged periods in very high gas concentrations, as these conditions can permanently reduce sensitivity.
Do not block or contaminate the sensor venting surface. Avoid impacts, excessive vibration, water, prolonged condensation and disassembly of the sensor or module. The instrument is specified for operation from −10 to +55 °C and should be used in accordance with the manufacturer’s warnings and the safety rules applicable to the installation or area being inspected.
| Electrónica Embajadores reference | IN7A002 |
| Brand | FNIRSI |
| Model / manufacturer reference | GD-02 |
| Type | Portable combustible-gas detector |
| Detectable gases | Methane, propane and isobutane |
| Methane range | 0–50,000 ppm |
| %LEL range | 0–100% LEL |
| Resolution | 1 ppm / 1% LEL |
| Display | 2.0-inch colour |
| Probe | Flexible, approximately 360 mm |
| Warm-up time | Approximately 15–16 s |
| T90 response time | <5 s |
| T10 recovery time | <10 s |
| Sampling time | ≈0.5 s |
| Stated sensor service life | >3 years |
| Operating temperature | −10 to +55 °C |
| Displayed environmental parameters | Temperature and relative humidity |
| HOLD function | Yes |
| Trend curve | Yes; refresh every 0.5 s |
| Alarm thresholds | Configurable high and low |
| Alarm outputs | Indicator light, vibration and buzzer |
| Alarm log | Up to 30 events with date, time and type |
| Built-in torch | Yes |
| Interface themes | Light / dark |
| Device languages | Simplified Chinese and English |
| Date and time | Configurable |
| Display brightness | Adjustable |
| Volume | Adjustable |
| Sleep mode | Configurable |
| Automatic power-off | Configurable |
| Factory reset | Yes |
| Firmware update | Via USB-C and Bootloader |
| Interface | USB-C |
| Approximate dimensions | 63 × 28 × 139 mm plus 360 mm probe |
| Approximate weight | 296 g |
| Package contents | GD-02 detector, USB-C charging cable, storage case, user manual and packaging box |
| Standard stated in manual | GB 16808-2008 |
| Silicone-compound precaution | Avoid adhesives, hairspray, silicone materials and other volatile silicon compounds |
| Corrosive-gas precaution | Avoid high concentrations of H₂S, SOx, Cl₂ and HCl |
| Liquid precaution | Do not wet, immerse or allow liquids onto the sensor |
| High-concentration precaution | Do not apply lighter gas directly or leave the sensor for prolonged periods in high concentrations |
| Sensor maintenance | Keep the venting surface clean and unobstructed; do not dismantle the sensor or alter the module |